Hawke 501/453 Universal dual certified cable glands are Group II Hazardous Area certified. Suitable for internal and external use they provide armour clamping for all armour/braid types using one clamping arrangement.
These glands provide a diaphragm seal on the cables inner sheath which will not damage cable that has 'cold flow' characteristics. They additionally provide an outer deluge seal to prevent moisture ingress to the cable armour/braid and a cable retention, low smoke & fume, zero halogen seal onto the cable outer sheath.
Kit includes; gland, locknut, earthtag, nylon washer and serrated washer
Technical Summary
Cable Type: Single wire armour 'W', wire braid 'X', steel tape armour 'Z', elastomer and plastic insulated cables
Thread: "O" M20²
Temperature Range: -60°C to +80°C
Certification: Exdb IIC Gb, Exeb IIC Gb, ExnR IIC Gc, Extb IIIC Db
Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X
Deluge Protection: DTS01
Zones: Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC
Full technical details available on the Specification Tab